City of Alliance, Ohio
Mayor Toni E. Middleton
Home of the Scarlet Carnation
Stark County Sites State of Ohio Sites Federal Sites Streets & Water Other Alliance Sites















2002 WATER QUALITY DATA

CONTAMINANT

VIOLATION

YES/NO

MAX

LEVEL FOUND

RANGE

MCLG

MCL

YEAR AVERAGE

LIKELY SOURCE OF CONTAMINATION

Microbiological Contaminants

Turbidity

NO

0.75 NTU

0.04-0.75 NTU

TT

SEE

[A]

0.10 NTU

Soil Run-Off
Total Coliform

NO

1 positive sample

(ND)-1 positive

(ND)

SEE

[B]

>1

Naturally present in the environment
Total Organic Carbon

NO

1.22

1.22-1.86

N/A

TT

1.51

Naturally present in the environment.

[A] The turbidity limit is 0.3 NTU in 95% of the daily samples and shall not exceed 1 NTU at any time

[B] Any presence of coliform bacteria in > 5% of the monthly samples

Inorganic Contaminants (Regulated at the Treatment Plant)

Nitrate

NO

0.88 mg/l

<0.10-0.88 mg/L

10 mg/L

10 mg/l

0.35 mg/l

Run-Off from fertilizer use and animal grazing

Fluoride

NO

1.30 mg/l

0.74-1.30 mg/L

4 mg/L

4 mg/L

1.01 mg/L

Erosion of natural deposits, additive which promotes strong teeth
Chlorite

NO

0.61 mg/l

0.0-0.61 mg/l

0.8 mg/l

1.0 mg/l

0.23 mg/l

By-product of drinking water Chlorination.
Barium (ppb) NO

40 ug/l

N/A

200 ug/l

200 ug/l

40 ug/l

Refineries, drilling,erosion

(Regulated at Your Tap)

Copper

NO

90th percentile

110.0 ppb

<10 – 220 ppb

1300 ppb

AL=

1300 ppb

65.6 ppb

Corrosion of household plumbing systems
Lead

NO

90th percentile

4.4 ppb

< 2.0 – 8.5 ppb

15 ppb

AL=15 ppb

1.3 ppb

Corrosion of household plumbing systems

Note: Lead and copper monitoring is only required once in every three year monitoring period. The monitoring period was

completed in 2001. There were NO samples that exceeded 15ppb of lead and NO samples exceeded 1300 ppb of copper in 2001.

Volatile Organic Contaminants (Regulated at the Treatment Plant)

Chloroform

Bromoform

Bromodichloromethane

Dibromochloromethane

NO

NO

NO

NO

18.4 ppb

<0.5 ppb

12.7ppb

7.0 ppb

12.0 – 18.4

< 0.5

8.4 – 12.7

4.0 – 7.0

N/A

N/A

N/A

N/A

100 ppb

15.1 ppb

<0.5 ppb

10.8 ppb

5.5 ppb

By-Product of drinking water chlorination

Volatile Organic Contaminants (Regulated in the Distribution System)

TTHMs

Total Trihalomethanes

NO

66.0 ppb

55.4-66.0

0

80

ppb

59.6 ppb

By-Product of drinking water chlorination

Haloacetic Acids(HAA)

NO

25.4 ppb

23.5-25.4

ppb

60.0

ppb

N/A 24.3 ppb

By-Product of drinking water disinfection.

Radioactive Contaminants (Regulated at the Treatment Plant)

Gross Alpha

PCi/L

NO

< 3 pCi/L

NA

0

15 pCi/L

< 3 pCi/L

Erosion of natural deposits

Gross Beta

PCi/L

NO

7.7 pCi/L

NA

0

Al=50 pCi/L

7.7 pCi/L

Decay of natural and man made deposits

Note: Radioactive monitoring is only required once a year.

Synthetic Organic Contaminants (Regulated at the Plant)

Atrazine (ppb)

No

0.36 ppb

<0.3-0.36 ppb

3.0 ppb

 

3.0ppb

<0.3 ppb

Runoff from herbicide used on row crops

Residual Disinfectants

Chlorine

No

1.46 mg/l

1.27-1.46 mg/l

4 mg/l

4 mg/l

1.38 mg/l

Water additive used to control microbes
Chlorine dioxide

No

0.18 mg/l

0.0-0.18 mg/l

0.80 mg/l

0.80 mg/l

0.02 mg/l